Flow Controls fc_navi_b
| FlowCon AB | FlowCon K | FlowCon SH | ISOLATOR "R" | AHU Wafer | Uni-Flange | CL 150/300 Wafer | Cartridge | FlowCon SM |
Flowcon Automatic flow control cartridges
Specification and Construction Materials
1.Valve housing

2.Orifice Cup

3.Regulation unit

4.Spring

5.Valve Cover

6.O-rings
DZR brass (Enkotal ®)

Poly Oxy Methaline

Poly Oxy Methaline and Hydrogenated Acrylonitrile-Butadience-Rubber

Stainless steel (AISI 302)

DZR brass (Enkotal ®)

Acrylonitrile Butadience-Rubber and Ethylene Propylene Diene-Rubber
FlowCon AB_DN 15/20
Cartridge A B
Pressure Differential [kPa] 22 - 300 30 -410
[psi] 3 - 44 4.4 - 60
Flow Rate [liters/sec] 0.023 -0.344 0.024 - 0.403
[GPM] 0.25 - 5.9 0.29 - 7.0
Accuracy +/- 5% +/- 5%
Static pressure [kPa] 2500
[psi] 360
Temperature rating [Celsius] -30 / +100
[Fahrenhelt] -22 / +212
Pressure drop data Note:For pump head calculations,add the minimum pressure
differential for the index circuit to the other components pressure
losses.(i.e.valves,coil,etc..)
Automatic flow control [kPa] 22 30
Valve kv-value 2.6
previous next